ABSTRACT
In this paper a new digital relaying algorithm is introduced for the protection of synchronous generators against loss of field conditions. The new algorithm is based on measuring the three-phase reactive power output of the machine, and monitoring the direction and magnitude of the reactive power at the machine terminals. The protection algorithm is designed such that it can provide a reliable protection against loss of field conditions and remains stable during recoverable power system swing conditions. While the new relay produces trip signal for partial loss of field conditions causing the machine to loose its stability, it remains stable for partial loss of field conditions which can be corrected via machine excitation and VAR systems.
الملخص
سيتم فى هذه الورقة عرض منظومة وقاية جديدة لحماية المولدات التزامنية عند تعرضها لفقد التحريض المغناطيسى. تعتمد هذه المنظومة فى عملها على متابعة القدرة غير الفعَّالة عند أطراف الآلة عن طريق تحديد إتجاه سريانها ومقداره ومن ثم يمكن الحكم على وضعية التحريض المغناطيسى بالمولد. صممت هذه المنظومة لتوفـر حماية أكيدة للمولد عند فقد التحريض المغناطيسى مع التأكيد على بقاء تلك المنظومة مستقرة عند حدوث أعطاب إنتقالية شديدة أخرى داخل أو خارج المولد.
برهنت هذه المنظومة من خلال المحاكاة بالحاسوب على مقدرتها على إكتشاف الفقد النسبى لبعض ملفات التحريض المغناطيسى التى قد ينتج عنها خروج الآلة عن الإستقرار مع الشبكة وفى ذات الوقت بقيت هذه المنظومة مستقرة عند الفقد الجزئى لملفات التحريض المغناطيسى التى يمكن معالجتها دون أن تتسبب فى خروج الآلة عن الإستقرار.